Thứ Năm, 25 tháng 8, 2016

Trung tâm báo cháy Tyco 20-30 kênh P401-A0103 / P401-A0104

extensive control capability for areas requiring variable IDC zones. The conventional fire control panel is also compatible with conventional input devices such as two- and four-wire smoke detectors, manual call points, waterflow switches, tamper switches, and other normally - open contact devices.



Optional Functions

䦬 Additional Notification and Control circuits

䦬 Alarm valve pressure switch and temper switch monitoring

䦬 Cross zoning

䦬 Fan control and monitor

䦬 Damper monitor and control

䦬 Smoke window monitor and control

䦬 Fire Door and Shutter monitor and control



Standard Functions



5/10/20/30 Initiating Device Circuits

Main Bell (1 circuit) and Local Bell (1 circuit)

Indicating Lamp (1 circuit)

Emergency Announcement (1 circuit)

Telephone (1circuit)

Exit Light (1 circuit)

Generator Manual Actuation

Hydrant pump monitoring and controlling (2 circuits)

Sprinkler Pump monitoring and control (2 circuits)

Pressure switch monitoring (4 circuit)

Water tank Low Level switch monitor (1circuit)



Features



Installer friendly designed

Korea and China approval

Simplifies maintenance.

Enhances fire detection and eliminates nuisance.

Open circuit fault monitoring.

Integral power back up battery

Available telephone handset as an option



Specifications



Power Source AC 110V / 220V, 50 ~60Hz

Control voltage DC 24V (‚20%)

Power Consumption 150 VA MAX.

Contact capacity Max. 1A

Emergency power DC 24V, Ni-cd 0.5Ah battery (5 circuit control panel)

DC 24V, Ni-cd 1.2Ah battery (10/20/30 circuit control panels)

Stand-by time Supervision: More 60 minutes, Alarm : More 10 minutes

Ambient condition -10°C ~ 50°C, Max. 85% Rh

Dimension 283mm x 340mm x 86.5mm (5 circuit control panel)
400mm x 600mm x 172mm (10/20/30 circuit control panels)Trung tâm báo cháy Tyco 20-30 kênh P401-A0103 / P401-A0104

Không có nhận xét nào: